Omron SYSDRIVE RX Series User Manual page 332

High-function general-purpose inverter
Table of Contents

Advertisement

5-1 Protective Functions and Troubleshooting
Function List of the DIP Switches on the PG Board (3G3AX-PG01)
DIP switch
SWENC
SWR
5
•Protection function display when the digital command board (3G3AX-DI01) is mounted
Name
3G3AX-DI01
error
Note: Input mode is determined by the combination of DIP and rotary switches. Check the settings of the DIP and
rotary switches on the digital command board for any abnormal operation.
5-7
Switch No.
Disconnection detection enabled when the encoder A/B-phase is not
ON
connected
1
Disconnection detection disabled when the encoder A/B-phase is not
OFF
connected
Disconnection detection enabled when the encoder Z-phase is not
ON
connected
2
Disconnection detection disabled when the encoder Z-phase is not
OFF
connected
With the termination resistor between SAP and SAN (150 Ω)
ON
1
OFF Without the termination resistor between SAP and SAN
With the termination resistor between SBP and SBN (150 Ω)
ON
2
OFF Without the termination resistor between SBP and SBN
Description
Shuts off the output and displays an error if a timeout occurs in
communication between the Inverter and digital command board.
Description
Display on Digital Operator
ek6k0.
ek7k0.