Pulse Train Frequency Input

This function allows you to use a pulse train input to the SAP-SAN terminals as frequency reference
or PID feedback value in each control mode.
(This function can be used in all control modes.)
Set the input frequency at the maximum frequency in pulse train frequency scale P055.
The analog input start/end function cannot be used. To limit the input frequency, use pulse train fre-
quency bias amount P057 and pulse train frequency limit P058.
Parameter No.
Function name
P055
Pulse train frequency scale
Pulse train frequency filter
P056
time constant
Pulse train frequency bias
P057
amount
P058
Pulse train frequency limit
Frequency reference
A001
selection
A076
PID feedback selection
Operation frequency input
A141
A setting
Operation frequency input
A142
B setting
Pulse train frequency processing block
Frequency
Hz
measurement
Frequency scale (P055)
(1.0 to 50.0 kHz)
Note: The SWENC switch on PG Board is available for "OFF: encoder disconnection detection disabled".
4-3 Functions When Option PG Board (3G3AX-PG01) Is Used
1.0 to 50.0: Set the input frequency at the
maximum frequency.
0.01 to 2.00: Set a filter time constant for
pulse train input.
-100. to +100.
0. to 100.
06: Pulse train frequency
03: Pulse train frequency
07: Pulse train frequency
07: Pulse train frequency
Bias/Limit
Limit
%
1
1+sT
Bias
First-order lag filter (P056)
Data
Default setting
%
Hz
Maximum
frequency
(A004)
Unit
25.0
kHz
0.10
s
0.
%
100.
%
02
00
02
03
Frequency
reference
4-138
4