Voltage
Capacity
Max. fc (kHz)
5.5 kW
15
7.5 kW
15
11 kW
12
15 kW
12
18.5 kW
10
22 kW
7
30 kW
5
37 kW
10
45 kW
5
55 kW
5
75 kW
90 kW
110 kW
132 kW
200-V class
100
95
90
85
45, 55 kW
80
75
70
65
60
55
0.5 2
4
6
Carrier frequency (kHz)
•If the above maximum rated carrier frequency and the derating value at 15 kHz are exceeded, the
Inverter may be damaged and/or the service life may be shortened.
Parameter Initialization
•You can initialize the rewritten set values and reset to the factory default.
•You can clear trip data.
•You cannot clear the P100 to P131 set values, RUN time, or power ON time.
Parameter No.
Function name
b084
Initialization selection
Initialization parameter
b085
selection
200-V class
Derating at fc = 15 kHz
100%
100%
90% (41.4 max.)
95% (60.8 A max.)
90% (68.4 A max.)
70% (66.5 A max.)
80% (96.8 A max.)
75% (108.7 A max.)
70% (127.4 A max.)
70% (154 A max.)
22 kW
18.5 kW
11 kW
15 kW
30 kW
37 kW
8
10
12
14
15
00: Clears the trip monitor
01: Initializes data
02: Clears the trip monitor and initializes
data
00: Do not change
400-V class
Max. fc (kHz)
15
100%
15
100%
15
100%
14
95% (30.4 A max.)
10
90% (34.2 A max.)
6
75% (36.0 A max.)
10
75% (43.5 A max.)
8
80% (60.0 A max.)
9
75% (68.2 A max.)
6
60% (67.2 A max.)
6
85% (126.7 A max.)
4
75% (132.0 A max.)
6
70% (151.9 A max.)
3
60% (156.0 A max.)
400-V class
90 kW
75 kW
100
95
90
85
80
132 kW
75
70
65
110 kW
60
55
0.5 2
4
6
8
Carrier frequency (kHz)
Data
4-2 Function Mode
Derating at fc = 15 kHz
(75 to 132 kW is for 10 kHz)
45 kW
30 kW
15 kW
18.5 kW
37 kW
22 kW
55 kW
10
12
14
15
Default setting
Unit
00
00
4-66
4