4-2 Function Mode
Parameter
Data
No.
4
C001 to
C008
•You can select NO- or NC-contact input for each multi-function input terminal.
Parameter
No.
C011 to
C018
FW terminal operation
C019
Related functions
4-79
Function name
55
FOC : Preliminary excitation
56
Not used
57
Not used
58
Not used
59
Not used
60
Not used
61
Not used
62
Not used
63
Not used
65
AHD : Analog command held
66
CP1 : Position command selection 1
67
CP2 : Position command selection 2
68
CP3 : Position command selection 3
69
ORL : Zero return limit signal
70
ORG : Zero return startup signal
71
FOT : Forward driving stop
72
ROT : Reverse driving stop
73
SPD : Speed/Position switching
74
PCNT : Pulse counter
75
PCC : Pulse counter clear
no
NO
: No allocation
Function name
00: NO contact
01: NC contact
Multi-function input
• You can set NO- and NC-contact inputs
operation selection
individually for multi-function input terminals S1 to
S8 and the FW terminal.
• NO contact: "ON" with the contact closed, "OFF"
with the contact open.
• NC contact: "ON" with the contact open. "OFF"
selection
with the contact closed.
• A terminal with reset (RS) setting functions as NO
contact only.
Reference item
Preliminary excitation function
Analog command held
Absolute position control mode
Multi-function pulse counter
Data
C001 to C008
Page
4-116
4-91
4-133
4-136
4-134
4-91
Default
Unit
setting
00
00