Omron SYSDRIVE RX Series User Manual page 132

High-function general-purpose inverter
Table of Contents

Advertisement

4-2 Function Mode
•If the free V/f setting is enabled, the functions of torque boost A041/A241, base frequency A003/
A203/A303, and maximum frequency A004/A204/A304 are disabled. (Free V/f frequency 7 is
regarded as the maximum frequency.)
Parameter No.
b100
Free V/f frequency 1
b102
Free V/f frequency 2
b104
Free V/f frequency 3
b106
Free V/f frequency 4
b108
Free V/f frequency 5
b110
Free V/f frequency 6
4
b112
Free V/f frequency 7
b101
Free V/f voltage 1
b103
Free V/f voltage 2
b105
Free V/f voltage 3
b107
Free V/f voltage 4
b109
Free V/f voltage 5
b111
Free V/f voltage 6
b113
Free V/f voltage 7
Related functions
* Even if free V/f voltages 1 to 7 are set to 800 V, the Inverter cannot output voltage higher than
the input voltage or the value of the motor voltage selection.
Use thorough caution to verify that the output characteristic setting is proper. An improper setting
causes overcurrent during acceleration or deceleration, or vibration of the motor and/or machine.
4-23
Function name
0. to Free V/f frequency 2
0. to Free V/f frequency 3
0. to Free V/f frequency 4
0. to Free V/f frequency 5
0. to Free V/f frequency 6
0. to Free V/f frequency 7
0. to 400.
0.0 to 800.0
(Example)
Output voltage (V)
V7
V6
V5
V4
V1
V2, V3
0
f1
Output
voltage (V) V7
V6
0
f6
Data
Description
Set frequencies for
each break point.
Set output voltages
for each break point.
A044, A244, A344
f2
f3
f4
f5
f6
f7
Select the voltage or motor
voltage available for output.
f7
Output frequency (Hz)
Default setting
0
0.0
*
Output frequency (Hz)
Unit
Hz
V

Hide quick links: