6.12
Configuring Smart Meter Using Pushbuttons,
Setting Upper Display
Values
ATTENTION
Table 36
Setting Upper Display Value for Smart Meter Display
Step
1
Press UPPER VALUE button to initiate upper
display limit setting function.
2
Press UPPER VALUE button again within 5
seconds. Otherwise, meter exits limit setting
function.
6/05
ST 3000 Release 300 and SFC Model STS103 User's Manual
The procedure in Table 36 outlines the steps for setting the upper
display limit to represent the 100 percent (URV) output of the
transmitter.
This procedure applies only for Flow units (GPM or GPH) in a
transmitter configured for SQUARE ROOT output conformity, or
CUSTOM unit in a transmitter configured for linear or square root
output conformity.
Action
Meter Display
If upper limit display value was previously set,
KNOWN VALUE indicator lights and set value
flashes in display.
Display shows magnitude range selection.
V A R
SEL.
%
0
19 .99
ANALOG
ATTENTION
The magnitude range
selection only applies for setting the display
limits. This selection does not affect the
normal operation of the meter. During normal
operation, the display is automatically ranged
to provide the best precision possible.
Continued
UPPE R
VALUE
100
UNITS
S E T
LOWER
VALUE
Continued on next page
115