Honeywell ST 3000 User Manual page 178

Smart transmitter release 300 and smart field communicator model sts103
Hide thumbs Also See for ST 3000:
Table of Contents

Advertisement

8.6
Monitoring Local Smart Meter Display
Display description
Table 50
Description of Display Indicators Shown in Figure 51
Display Indicator
17-Segment Bargraph
Digital Readout
%
FLOW
OUTPUT MODE
CHECK STATUS
164
ST 3000 Release 300 and SFC Model STS103 User's Manual
Figure 51 shows a Local Smart Meter display with all its indicators and
segments lit for reference and Table 50 gives a brief description of what
the indications mean.
Figure 51
Display With All Indicators Lit.
V A R
SEL.
SP AN
ZERO
Gives a gross indication of the transmitter's PV output from 0 to
100%.
Gives an indication of the transmitter's PV output in either percent
of span or actual engineering units. The display range is
±19,990,000 and it is automatically ranged to provide the best
precision possible within the limits of the display. A second
decimal place expands the precision of range values within
±19.99 to 1/100th of a unit.
Digital readout represents output in percent of span. This is the
default engineering units selection.
Transmitter is configured for Square Root output conformity.
Transmitter is in its output mode and it is not sending a real PV
signal.
Transmitter in DE mode is broadcasting a critical status or
transmitter in Analog mode has an output that is less than –2.0%
or greater than 106%. Use the SFC to check transmitter's status.
%
0
18 8
8
0
-
.
.
OUTPUT MODE
ANALOG
CHECK STATUS
K
KNOWN VALUE
What It Means When Lit
UPPE R
VALUE
100
UNITS
%
S E T
FLOW
In H O
2
LOWER
GPH mmHg
VALUE
A
GPM PSI
Continued on next page