6.12
Configuring Smart Meter Using Pushbuttons,
Setting Lower Display
Values, continued
Table 35
Setting Lower Display Values for Smart Meter Display
Step
1
You have completed units selection in Table
33 and U-L appears on the display. Press
LOWER VALUE button to initiate lower
display limit setting function.
ATTENTION
applicable for Custom (EUF) engineering unit
selection in a transmitter configured for
LINEAR output conformity.
The lower display value for transmitters
configured for SQUARE ROOT output
conformity is fixed at zero (0.00) and cannot
be changed.
2
Press LOWER VALUE button again within 5
seconds. Otherwise, meter exits limit setting
function.
6/05
ST 3000 Release 300 and SFC Model STS103 User's Manual
Action
This procedure is only
Meter Display
If lower limit display value was previously set,
KNOWN VALUE indicator lights and set value
flashes in display.
V A R
SEL.
%
0
0 . 0
0
ANALOG
KNOWN VALUE
Previously set
value flashes in
display and
indicator lights
Display shows magnitude range selection.
V A R
SEL.
0
%
19 .99
ANALOG
ATTENTION
The magnitude range
selection only applies for setting the display
limits. This selection does not affect the
normal operation of the meter. During normal
operation, the display is automatically ranged
to provide the best precision possible.
Continued
UPPER
VALUE
100
UNIT S
S E T
LOWER
VALUE
UPPE R
VALUE
100
UNITS
S E T
LOWER
VALUE
Continued on next page
111