5.2
Establishing Communications,
Starting
communications
Table 17
Starting Communications with Transmitter.
Step
Press Key
1
2
3
DE READ
A
ID
4
NON-VOL
ENTER
(Yes)
52
ST 3000 Release 300 and SFC Model STS103 User's Manual
Once you connect the SFC to the transmitter or loop wiring, you are
ready to start communicating with the transmitter. The procedure in
Table 17 outlines the steps for communications with an ST 3000
transmitter without an assigned tag number.
Read Display or Action
Slide power switch on left side of SFC to
ON position.
P U T
L O O P
OR
D E
X
M
T
R
P
T A
G
N
O
.
T R I P S
S E C U R E D ?
OR
Go to Step 5
Confirms that "TRIPS" are secured. Go
to Step 5 for display response.
Continued
SFC runs its self check and displays
initial prompt.
If this prompt appears, transmitter is
I N
M A N
in Analog mode of operation. This is
the factory default mode of
operation setting. Put your control
loop in the manual mode of
operation before initiating SFC
communications. Note that you must
do this separately through the
receiving device in the loop.
If this prompt appears, transmitter is
R E
S
S
I
D
in Digital (DE) mode of operation.
Be sure any switches that may trip
alarms or interlocks associated with
?
analog loop are secured or turned
off. Go to Step 4.
This prompt does not appear for
transmitters operating in DE mode.
See DE transmitter display response
in Step 5.
Required for transmitters operating
in analog mode only.
Description
Continued on next page