Pressure Measurement With Dp Transmitter; Figure 40 Typical Piping Arrangement For Pressure Measurement With Dp Type Transmitter; Table 40 Starting Up Dp Transmitter For Pressure Measurement With Sfc - Honeywell ST 3000 User Manual

Smart transmitter release 300 and smart field communicator model sts103
Hide thumbs Also See for ST 3000:
Table of Contents

Advertisement

7.5

Pressure Measurement with DP Transmitter

Procedure
Figure 40
Typical Piping Arrangement for Pressure Measurement with DP Type Transmitter.
Table 40
Starting Up DP Transmitter for Pressure Measurement With SFC
Step
Press Key
1
2
3
132
ST 3000 Release 300 and SFC Model STS103 User's Manual
The procedure in Table 40outlines the steps for starting up a differential
pressure (DP) type transmitter in a pressure measurement application.
Refer to Figure 40 for the piping arrangement identification and Figure
38 for typical SFC and meter connections.
H
HP side
HP Vent
Read Display or Action
Connect SFC across loop wiring and
turn it on. If possible, locate SFC where
you can also view receiver instrument in
loop. If you want to verify transmitter
output, connect a precision milliammeter
or voltmeter in loop to compare
readings.
Close valve D.
Open plug C and valve A to apply head
pressure H to meter body. Then, open
LP vent.
Valve D
Plug C
Valve A
Differential
Pressure
Transmitter
LP side
LP Vent
Description
See Figure 38 for sample SFC and
meter connections in a typical
analog loop with a differential
pressure type transmitter.
See Figure 40 for sample piping
arrangement.
Allow system to stabilize at head
pressure.
Continued on next page