Setting Range Values Using Sfc; Table 25 Keying In Lrv And Urv - Honeywell ST 3000 User Manual

Smart transmitter release 300 and smart field communicator model sts103
Hide thumbs Also See for ST 3000:
Table of Contents

Advertisement

6.7

Setting Range Values Using SFC

Background
ATTENTION
Procedure 1
Table 25
Keying in LRV and URV
Step
Press Key
1
E
LRV
0%
2
S
5
3
NON-VOL
ENTER
(Yes)
4
F
URV
100%
6/05
ST 3000 Release 300 and SFC Model STS103 User's Manual
You can set the LRV and URV by either keying in the desired values
through the SFC keyboard or applying the corresponding LRV and
URV pressures directly to the transmitter.
• We factory calibrate ST 3000 Smart Transmitters with inches of
water ranges using inches of water pressure referenced to a
temperature of 39.2°F (4°C).
• For a reverse range, enter the upper range value as the LRV and the
lower range value as the URV. For example, to make a 0 to 50 psi
range a reverse range, enter 50 as the LRV and 0 as the URV.
• The URV changes automatically to compensate for any changes in
the LRV and maintain the present span (URV – LRV).
• If you must change both the LRV and URV, always change the LRV
first.
Table 25 gives the procedure for the range values for a sample 5 to 45
inH
O at 39.2°F (4°C) range.
2
Read Display or Action
L R V
1
P T
"
Ø .
Ø Ø Ø Ø
L R V
1
P T
5 _
"
L R V
1
P T
S
F
C
W
O R K
I
L R V
1
P T
"
5 .
Ø Ø Ø Ø
U R V
1
P T
"
1
Ø 5
.
Ø Ø
Present LRV setting. (Pressure for 4
3 Ø 1 1
mAdc (0%) output.)
H 2 O _ 3 9 F
Key in desired LRV setting. (It is not
3 Ø 1 1
necessary to key in a decimal point
H 2 O _ 3 9 F
and zeros for a whole number.)
Message exchange is working.
3 Ø 1 1
N G
.
.
.
New LRV setting stored in
3 Ø 1 1
transmitter's working memory.
H 2 O _ 3 9 F
Present URV setting. (Pressure for
3 Ø 1 1
20 mAdc (100%) output.)
H 2 O _ 3 9 F
Description
Continued on next page
81