Diagnostic And Troubleshooting; Analog Meter; Smart Meter; Figure 15: Horizontal Style Bargraph - Honeywell STT25D Operator's Manual

Stt 3000-series stt250 smart temperature transmitter
Table of Contents

Advertisement

6.4

Diagnostic and Troubleshooting

6.4.1 Analog Meter

The Analog Meter is an irreparable item. If it reads at the bottom of the scale with a
known input, check that the connections are good and that the voltage across the
meter/diode terminals is 0.5 to 0.7 V. This reading confirms that the delicate moving
coil connections have been damaged and that the meter should be replaced.

6.4.2 Smart Meter

Every time power is cycled to the transmitter/meter combination, the Smart Meter runs
a self test to check internal operations and switches on all display segments as shown
in Figure 15 for up to 10 seconds. This enables confirmation of their operation.
6.4.2.1 Failed self test
If the self test fails, the display will go blank (i.e. revert to the unpowered display
showing only the basic bargraph outline). Note that some of the temporarily switched
on segments should only be seen with an STT250 in this initial self check e.g. "K" for
a 1,000 engineering unit multiplier (only for readings over 20,000), "GPH", "GPM",
"mmHg", "PSI", "%", "FLOW" and "inH
transmitters).
ANALOG" is switched on the LCD if the transmitter output signal is 4-20 mA analog.
The "Normal" display should have a partially switched on bargraph corresponding to
the transmitter % of span output signal and the corresponding digital display in % of
the selected units.
Smart Temperature Transmitter STT250 – Operator Manual
17-SEGMENT BARGRAPH
(0 to 100%)
DIGITAL READOUT
(-19990 to +19990)
STATUS MESSAGE

Figure 15: Horizontal Style Bargraph

ENGINEERING UNIT
INDICATOR
PUSH BUTTON LOCATION
0" (only used for flow and pressure
2
29