6.12
Configuring Smart Meter Using Pushbuttons,
Button Pushing
Summary
Figure 37
Button Pushing Summary for Setting Lower and Upper Display Limits.
Is
EUF in
or
LINEAR
SQUARE ROOT
mode?
LINEAR
Mode
Set Lower
Range Value
Lower
Value
If display limit was previously set, KNOWN VALUE indicator lights
and set value flashes in display.(Note that lower display limit is
fixed at zero (0.00) for units in SQUARE ROOT mode.)
Lower
Value
Set magnitude range: 19.99, 199.9, 1999,
19.99K, 199.9K, 1999K, 19990K
Lower
Value
122
ST 3000 Release 300 and SFC Model STS103 User's Manual
Figure 37 shows button pushing summary for the smart meter display to
set the lower and upper display limits.
A
Is
NO
EUD or EUE
selected?
YES
SQUARE ROOT
Mode
Set Upper
Range Value
Upper
Value
Upper
Value
Upper
Value
Set active digit value 0 to 9
Lower
Value
No
Is "1" digit active?
Yes
Set 1 digit to BLANK
Lower
Value
Set sign segment
BLANK for positive
values
Lower
Value
Are both lower and
upper display limit
values set?
Yes
End
Continued
Upper
Value
Set 1 digit to 1
Upper
Value
Set sign segment
to minus sign (-) for
negative values
Upper
Value
No
6/05