Figure 25 Flowchart - St 3000 Pressure Transmitter Configuration - Honeywell ST 3000 User Manual

Smart transmitter release 300 and smart field communicator model sts103
Hide thumbs Also See for ST 3000:
Table of Contents

Advertisement

6.2
Overview,
Configuration
decision summary
Figure 25
Flowchart — ST 3000 Pressure Transmitter Configuration.
Start
Have you
assigned a unique
"tag number" for
the transmitter?
YES
Establish communications and
enter assigned Tag Number at
SFC configuration prompt TAG
NO.
Do you know if
output is to represent
linear or square root
calculation?
YES
Select LINEAR or SQUARE ROOT
through SFC configuration
prompt CONFORMITY.
A
6/05
ST 3000 Release 300 and SFC Model STS103 User's Manual
Continued
The flowchart in Figure 25 summarizes the typical entries/selections
decisions associated with configuring an ST 3000 pressure transmitter.
NO
Assign a unique tag number consisting of up to 8
alphanumeric characters to identify this transmitter.
See procedure in Table 21 for entry details.
Press [
ID
required, to call up SFC prompt TAG NO. Use [
key to toggle between Alpha mode and Numeric mode to
enter alphabetic characters and numbers, respectively,
through SFC keys.
NO
Determine if transmitter's output is to represent a
straight linear calculation or a square root calculation
for flow measurements.
See procedure in Table 22 for selection details.
Call up SFC configuration prompt CONFORMITY and select
menu item LINEAR or SQUARE ROOT.
] key and acknowledge TRIPS SECURED prompt, if
/
]
NUM
ALPHA
Continued on next page
67

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents