Advertisement

2. Transmitter Mounting
2.6. Rotate display
CAUTION
Take precautions against electrostatic discharge to prevent damaging the
display/sensor module.
Step
1
Honeywell recommends that the transmitter be removed from service and moved to a clean
area before servicing.
2
Loosen the M3 locking set screw on the display end-cap. See item 1 in Figure 9. Unscrew and
remove the end cap.
3
Loosen the two captive screws on the display/sensor module. See items 2 in Figure 9.
4
Rotate the display 90 or 180 degrees in either direction so the screws line up with the threaded
holes. Do not rotate more than 180 degrees or you could damage the wires behind the display.
5
Re-attach the display's two captive screws. Tighten to 0,4 – 0,6 N-m (3.5 – 5.3 lb-in.).
6
Replace end cap and tighten M3 locking screw.
12

Table 2-1 Display adjustment

2

Figure 9 Display rotation

OneWireless XYR 6000 Transmitters Quick Start Guide
Action
2
1
Revision 3
8/8/07