6.8
Setting Range Values Using Local Adjustments,
Continued
Procedure, continued
Figure 32
Typical Setup for Setting Range Values Using Local Zero and Span Adjustments.
+
Power
Supply
-
Receiver
250 Ω
6/05
ST 3000 Release 300 and SFC Model STS103 User's Manual
Table 27
Setting Range Values Using Local Zero and Span
Adjustments, continued
Step
10
Wait 30 seconds so that changes have been copied to the
transmitter's non-volatile memory.
11
Remove applied pressure and turn OFF transmitter power.
12
Replace end-cap on PWA side of electronics housing and tighten
lock.
13
Remove milliammeter from TEST terminals and replace end-cap and
tighten lock.
Turn ON transmitter power and check Local Smart Meter reading, if
14
applicable.
+
-
Field
Terminals
Action
ST 3000
Milliammeter
STR3015