6.11 Four Way Valve Abnormality (18 Class Only)
EA
Remote
Controller
Display
j
Outdoor Unit LED
A
Display
Method of
The liquid pipe thermistor and the outdoor heat exchanger thermistor are checked to see if they
Malfunction
function within their normal ranges in the operating mode.
Detection
Malfunction
Either of the following conditions occurs 6 minutes after the compressor has started.
Cooling operation
Decision
Conditions
Heating operation
Tde: outdoor heat exchanger temperature
Poor connector contact
Supposed
Defective thermistor
Causes
Defective outdoor unit PCB
Defective four-way valve, coil, or harness
Foreign substance mixed in refrigerant
Service Diagnosis
i
h
h
h
1
2
3
4
The lowest liquid pipe temperature among the rooms in operation –Tde > 5°C (41°F)
The highest liquid pipe temperature among the rooms in operation –Tde < 0°C (32°F)
Troubleshooting for Outdoor Unit