Troubleshooting for Outdoor Unit
6.20 Output Overcurrent Detection
L5
Remote
Controller
Display
j
Outdoor Unit LED
A
Display
Method of
An output overcurrent is detected by checking the current that flows in the inverter DC section.
Malfunction
Detection
A position signal error occurs while the compressor is running.
Malfunction
A speed error occurs while the compressor is running.
Decision
An output overcurrent signal is fed from the output overcurrent detection circuit to the
Conditions
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 5 minutes without any other error
Poor installation condition
Supposed
Closed stop valve
Causes
Defective power module
Wrong internal wiring
Abnormal power supply voltage
Defective outdoor unit PCB
Defective compressor