Anti-Icing Function - Daikin SUPER MULTI NX CTXS07JVJU Service Manual

Super multi nx g-series / j-series
Hide thumbs Also See for SUPER MULTI NX CTXS07JVJU:
Table of Contents

Advertisement

Troubleshooting for Outdoor Unit
6.5

Anti-icing Function

A5
Remote
Controller
Display
Outdoor Unit LED
A
5
Display
Method of
During cooling operation, indoor unit icing is detected by checking the temperatures sensed by the
Malfunction
indoor heat exchanger thermistor and room temperature thermistor that are located in a shut-down
room.
Detection
 In cooling operation, the both conditions (A) and (B) are met for 5 minutes.
Malfunction
Decision
Conditions
 If the error repeats, the system is shut down.
 Reset condition: Continuous run for about 60 minutes without any other error
 Wrong wiring or piping
Supposed
 Defective outdoor electronic expansion valve
Causes
 Short-circuited air
 Defective indoor heat exchanger thermistor
 Defective room temperature thermistor
163
1
4
2
3
3
4
4
4
(A) Room temperature – Indoor heat exchanger temperature  18°F (10°C)
(B) Indoor heat exchanger temperature  30.2°F (–1°C)
SiUS12-928_B
Service Diagnosis