Four Way Valve Abnormality - Daikin FTX-N Series Service Manual

Inverter pair: wall mounted type, floor standing type, duct connected type.
Hide thumbs Also See for FTX-N Series:
Table of Contents

Advertisement

Troubleshooting for Outdoor Unit
7.6

Four Way Valve Abnormality

EA
Error Code
Method of Error
The room temperature thermistor and the indoor heat exchanger thermistor are checked if they
Detection
function within their normal ranges in each operation mode.
Error Decision
The following condition continues over C seconds after operating for 5 minutes.
Conditions
 Cooling/Dry
 Heating
Outdoor temperature
–15°C (5°F) or higher
Lower than –15°C (5°F)
 If the error repeats, the system is shut down.
 Reset condition: Continuous run for about 60 minutes without any other error
Supposed
 Disconnection of four way valve coil
Causes
 Defective four way valve, coil, or harness
 Defective outdoor unit PCB
 Defective thermistor(s)
 Refrigerant shortage
 Water mixed in refrigerant
 Defective stop valve
161
A – B < –5°C (A – B < –9°F)
B – A < –5°C (B – A < –9°F)
A: Room thermistor temperature
B: Indoor heat exchanger temperature
09 class
C (seconds)
12 class
15 class
300
300
300
600
300
1400
SiUS091601EA
18 class
24 class
300
300
1400
1400
Part 6 Service Diagnosis