Troubleshooting for Outdoor Unit
6.17 Thermistor or Related Abnormality (Outdoor Unit)
H9, J3, J6, J8, J9, P4
Remote
Controller
Display
j
Outdoor Unit LED
A
Display
Method of
This type of error is detected by checking the thermistor input voltage to the microcomputer.
Malfunction
A thermistor error is detected by checking the temperature sensed by each thermistor.
Detection
The thermistor input is above 4.96 V or below 0.04 V with the power on.
Malfunction
J3 error is judged if the discharge pipe temperature is lower than the heat exchanger
Decision
Conditions
The system is shut down if all the units are judged as the J8 error.
Disconnection of the connector for the thermistor
Supposed
Defective thermistor corresponding to the error code
Causes
Defective heat exchanger thermistor in the case of J3 error (outdoor heat exchanger thermistor
Defective outdoor unit PCB
181
i
i
h
h
1
2
3
4
temperature.
in cooling operation, or indoor heat exchanger thermistor in heating operation)
SiUS12-928_B
Service Diagnosis