Daikin SUPER MULTI NX CTXS07JVJU Service Manual page 186

Super multi nx g-series / j-series
Hide thumbs Also See for SUPER MULTI NX CTXS07JVJU:
Table of Contents

Advertisement

SiUS12-928_B
Troubleshooting
24/32 class
Check No.15
Refer to P.196
Check No.18
Refer to P.198
Service Diagnosis
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Turn off the power.
Check the power supply voltage.
Voltage as rated?
YES
Check No. 18
Check the discharge pressure.
OK?
YES
Check the connection.
Electrical
components or
compressor harnesses
connected as
specified?
YES
Turn on the power.
Check the electrolytic capacitor
voltage.
320 ± 50 VDC?
YES
Turn off the power. Disconnect the
harnesses U, V, and W.
Check No.15
Check with the inverter checker (∗).
Any LED OFF?
NO
NO
NO
NO
NO
∗ Inverter checker
Part No.: 1225477
YES
Troubleshooting for Outdoor Unit
Correct the power supply.
Replace the stop valve.
Reconnect the electrical
components or compressor
harnesses as specified.
Replace the outdoor unit
PCB.
Correct the power supply or
replace the outdoor unit
PCB.
Replace the compressor.
(R15892)
178

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents