Main Functions
1.6
Automatic Operation
Outline
Automatic Cooling / Heating Function
When the automatic operation is selected with the remote controller, the microcomputer
automatically determines the operation mode as cooling or heating according to the room
temperature and the set temperature at start-up.
The unit automatically switches the operation mode to maintain the room temperature at the set
temperature.
Detail
1. The set temperature (Ts) determines the target temperature (Tt).
2. The target temperature (Tt) is calculated as;
3. Thermostat ON/OFF point and operation mode switching point are as follows.
4. During initial operation
CTXS/FTXS-L series
Target temperature –3.6°F (– 2.0°C) =
Thermostat OFF
Target temperature –4.5°F (–2.5°C)
Ex: When the target temperature is 25°C (77°F)
Other models
Target temperature –3.6°F (– 2.0°C) =
Thermostat OFF
Target temperature –4.5°F (– 2.5°C)
Ex: When the target temperature is 77°F (25°C)
41
Ts: set temperature (set by remote controller)
Tt: target temperature (determined by microcomputer)
Tr: room thermistor temperature (detected by room temperature thermistor)
C: correction value
(Ts = 64.4 ~ 86°F, 18 ~ 30°C).
Tt = Ts + C
where C is the correction value
C = 0°F (0°C)
(1) Heating Cooling switching point:
Tr Tt + +5.4°F (3.0°C) (CTXS/FTXS-L series)
Tr Tt + +4.5°F (2.5°C) (other models)
(2) Cooling Heating switching point:
Tr < Tt – –4.5°F (2.5°C)
(3) Thermostat ON/OFF point is the same as the ON/OFF point of cooling or heating operation.
Tr Ts : Cooling operation
Tr < Ts : Heating operation
Cooling 73.4°F (23°C): Thermostat OFF 71.6°F (22°C): Switch to heating
Heating 80.6°F (27°C): Thermostat OFF 82.4°F (28°C): Switch to cooling
Cooling 73.4°F (23°C): Thermostat OFF 71.6°F (22°C): Switch to heating
Heating 79.7°F (26.5°C): Thermostat OFF 81.5°F (27.5°C): Switch to cooling
.
Cooling Operation
Target temperature +5.4°F (+ 3.0°C)
Target temperature +3.6°F (+ 2.0°C) =
Thermostat OFF
Heating Operation
Cooling Operation
Target temperature +4.5°F (+ 2.5°C)
Target temperature +2.7°F (+ 1.5°C)
= Thermostat OFF
Heating Operation
SiUS12-928_B
(R16965)
(R16966)
Function and Control