Four Way Valve Abnormality - Daikin FTXG20LV1BW Service Manual

Inverter pair wall mounted type l-series
Hide thumbs Also See for FTXG20LV1BW:
Table of Contents

Advertisement

SiBE041401E

4.16 Four Way Valve Abnormality

EA
Error Code
Method of Error
The room temperature thermistor and the indoor heat exchanger thermistor are checked if they
function within their normal ranges in each operation mode.
Detection
Error Decision
A following condition continues over 1 ~ 10 minutes (depending on the model) after operating
for 5 ~ 10 minutes (depending on the model).
Conditions
< Cooling / Dry >
< Heating >
Supposed
Causes
Service Diagnosis
A – B < –5°C
B – A < –5°C
A: Room thermistor temperature
B: Indoor heat exchanger temperature
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 60 minutes without any other error
Disconnection of four way valve coil
Defective four way valve, coil, or harness
Defective outdoor unit PCB
Defective thermistor
Refrigerant shortage
Water mixed in refrigerant
Defective stop valve
Troubleshooting
78