Troubleshooting for Outdoor Unit
6.10 Input Overcurrent Detection
E8
Remote
Controller
Display
Outdoor Unit LED
A
5
Display
Method of
Detected by checking the input current value
Malfunction
Detection
The input current is at a certain value (depending on the condition) for 2.5 seconds.
Malfunction
The compressor halts if the error occurs, and restarts automatically after 3-minute standby.
Decision
Conditions
Outdoor temperature is out of operation range.
Supposed
Defective compressor
Causes
Defective power module
Defective outdoor unit PCB
Short circuit
Troubleshooting
Check No.15
Refer to P.196
Check No.17
Refer to P.198
Check No.18
Refer to P.198
169
1
3
2
4
3
3
4
4
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
∗ An input overcurrent may result from wrong internal wiring. If the system is interrupted by an input
overcurrent after the wires have been disconnected and reconnected for part replacement, check the
wiring again.
Check No. 17
Check the installation condition.
Start operation and measure the
input current.
Input current flowing
above its stop level?
YES
Turn off the power and disconnect
the harnesses U, V, and W.
Check No. 15
Check with the inverter checker (∗).
Any LED off?
NO
Turn off the power, and reconnect
the harnesses. Turn on the power
again and start operation.
Check No. 18
Check the discharge pressure.
NO
∗ Inverter checker
Part No.: 1225477
YES
SiUS12-928_B
Replace the outdoor unit
PCB.
Correct the power supply or
replace the outdoor unit
PCB.
(R15325)
Service Diagnosis