Connection to a PLC by the Host Link (RS-422A Type)

Port 1
DM32000
DM32001
DM32002
DM32003
2-5

Connection to a PLC by the Host Link (RS-422A Type)

2-5-1

Compatible PLCs

When Using the Host Link Method
38
The following table shows the words allocated in the DM Area and the set-
tings.
Allocated DM word
Port 2
DM32010
DM32011
DM32012
DM32013
Connect the NT11 to an OMRON PLC by using the RS-422A type host link
method.
If the distance between the NT11 and the PLC is greater than 15 m, this
method should be used. The maximum distance over which a connection can
be made is 500 m.
when using the RS-422A method, the host computer and PLC are usually
connected in a 1 to N ratio (more than one PLC), but in the special case of the
connection between the NT11 and PLC, the ratio is 1 to 1.
In order to make a connection to the PLC using the host link method (RS-
422A type), the "Comm. Type" memory switch of the NT11 must be set to the
host link, and the "Comm. Port" memory switch must be set to RS-422A. For
details on memory switch settings, refer to 3-7-1 Selecting the Host Commu-
nication Method (page 73).
Compatible Host Units
Some models and series of OMRON PLCs have the RS-422A type Host Link
function built in. With a CS series, CJ series, and CQM1H Board or Unit, and
CQM1H, the Host Link method can be used by installing a Serial Communica-
tions Board. In addition, some C200HX/HG/HE(-Z)E devices have an integral
CPU Unit that can be connected in the Host Link method by installing a Serial
Communications Board.
With the CPM2A and CPM2C, an RS-422A type of 1:1 NT Link can be con-
nected through a CPM1-CIF11 RS-422A Adapter.
Check the model and series of the PLC and the type of the installed Board or
Unit before making a connection.
Value
8000
Host Link mode, 2 stop bits, even parity, data
length 7 bits
0000
Baud rate 9,600 bps.
0007
Baud rate 19,200 bps.
0008
Baud rate: 38,400 bps.
0009
Baud rate: 57,600 bps.
000A
Baud rate: 115,200 bps.
0000
Transmit delay time 0 ms.
0000
No CTS control Unit No. 0 for Host Link
Section 2-5
Settings