Connection to a PLC by the Host Link (RS-232C Type)
Connecting to a C-series Host Link Unit
Connecting to a CVM1/CV-series Host Link Unit
28
C200H/C200HS/C200HE/HG/HX (-Z)E Rack-mounted Unit:
C200H-LK201-V1
Setting the Front Switches
Set each switch with a flat blade screwdriver so that the values or symbols in
the setting value window agree with the following.
LK201
XMT
RUN
RCV
ERROR
• Unit # (SW1, SW2)
SW1
SW2
0
0
• Command level, parity, and transfer code (SW4)
SW3
SW4
2
5
• Baud rate (SW3)
Setting the Rear Switches
ON
1
2
3
4
CTS selector switch
External
0 V (ON)
CVM1/CV-series Rack-mounted Unit: CV500-LK201
A CVM1/CV-series Host Link Unit (CV500-LK201) has two connectors (com-
munication ports 1 and 2). Either of these ports can be used for connection to
an NT11 by the RS-232C method. However, since the connectors at these
ports are of different types, a cable that matches the connector must be pre-
pared.
• Communication port 1
Communication port 1 is a 25-pin connector for RS-232C use only.
• Communication port 2
Communication port 2 is a 9-pin connector that allows selection of the
RS-232C or RS-422A method. When this port is used with the RS-232C
method, the I/O port selector switch on the front of the Unit must be set to
RS-232C (the upper position).
Set these switches to 0.
Set this switch to 2.
Set this switch to 5 to select 9,600 bps.
Set this switch to 6 to select 19,200 bps.
• 1-to-1/1-to-N selection (DIP switch)
Set pin 3 to ON.
• CTS selection (selector switch)
Set this always to 0 V (ON).
Section 2-4