Outline of Host Link/NT Link Operation
Symbol
C-series PLCs
E
*2
EM Area
,
current bank
E0_ to
---
EC_
Procedure
Reference
Example of Reading the Number of Currently Display Screen
11212
Screen switch
strobe flag
114
Allocation
CV-series PLCs
OK
EM Area,
current bank
---
---
*1 LR 00000 to LR 00199 are converted to CIO 01000 to CIO 01199.
*2 The EM Area is supported only by the C200HX/HG/HE (-Z)E PLCs.
The Auxiliary Area of the CVM1 and CV-series PLCs is allocated to system
functions, and it cannot be used for purposes other than system use.
The range of each memory area differs according to the PLC. Refer to Appen-
dix D Making the Cable on page 153.
1. Use the support tool to allocate the PT status notify area (PT to PLC) to
the PLC memory.
2. Create a PLC program to read the "currently displayed screen word" in the
PT status notify area when the "screen switch strobe flag" in the PT status
notify area has turned ON.
• The contents of the "currently displayed screen word" are updated also by
switching the screen by using the menu screen function of the NT11.
• For details on the menu screen function, refer to 4-7 Menu Screen Func-
tion (page 99).
This example gives a PLC program that reads the screen number each time
the screen is switched. In this example, the number of the previous screen is
also stored.
• Support tool settings
Make the following settings with the support tool:
PT status notify area: Word 0110
• PLC ladder program
@MOV(21)
DM0100
DM0101
@MOV(21)
110
DM0100
• Program operation
1. When the NT11 screen display switches and the screen switch strobe flag
(bit 11212) turns ON, the contents of DM0100 are transferred to DM0101.
The number of the previously displayed screen is stored in word 0101.
2. The new screen number notified by the NT11 is read and transferred to
DM0100. The number of the currently displayed screen is stored in
DM0100.
Allocation
CS/CJ-series PLCs
Not for Host
EM Area,
Link
current bank
---
EM Area,
EM banks 0 to C
(1)
Word for storing the number of the previous screen
(2)
Word for notifying the number of the currently displayed screen
Word for storing a new screen number
Section 5-2
Allocation
Not for Host
Link
Not for Host
Link