Omron CX-PROGRAMMER V9 - REV 12-2009 Operation Manual page 69

Table of Contents

Advertisement

OMRON
(1) Area and Start Word
(2) Master, Common
Send Words
(3) Each Node, Received
and Sent
(Same as (3).)
(Same as (3).)
(Same as (3).)
5. Click the Write Button to transfer the automatic data link setting.
• Adding Nodes while Data Links Are Running
Previous version (version 3.1)
Data link tables could not be
downloaded when data link
were running.
• Up to 62 Nodes for Wired Controller Link Units
Previous version (version 3.1)
Only a maximum of 32 nodes
could be used with Wired
Controller Link Units.
• Displaying Data Link Table Information for Data Link Table
Verification
Previous version (version 3.1)
Data link table verification
results were displayed in a
simple list in an Error List
Dialog Box.
• 100Base-TX for Ethernet Units
Previous version (version 3.1)
Only 10Base-T and 10Base-5 were
supported in Unit settings (CPU Bus Unit
setups).
(4) Participating nodes
Master node
Slave node
1a
1a
1a
1a
1b
1b
2
3
2
2
3
4
3
4
Nodes can be added while data links are running if both the following Units/Boards and
Repeater Units (CS1W-RPT01) are used.
Applicable
models:
Note: Refer to the Controller Link Operation Manual for the procedure to add nodes and
details on changing data link tables while data links are running.
A maximum of 62 nodes can now be used with Wired Controller Link Units.
• CS1W-CLK21-V1
Applicable
• CJ1W-CLK21-V1
models:
• 3G8F7-CLK21-V1 (-EV1)
Note: A CS1W-RPT01 Repeater Unit must be purchased separately to use 62 Controller
Link Units. Refer to the Controller Link Operation Manual for details.
When inconsistencies are detected in data link
verification, the number of inconsistent (failed)
nodes is displayed, and both the data link
settings within the selected PLC and those
with the inconsistencies indicated between
pointed parentheses (< >). (The size of the
dialog box can be changed.) Also, if reading is
not possible for verification, the reasons are
displayed.
The results can be pasted as text after clicking
a Copy Button.
100Base-TX is also supported for Ethernet Unit in the Unit settings (CPU Bus
Unit setups).
Applicable models: CS1W-ETN21, CJ1W-ETN21
Features of Chain Type 1:N Allocation
Data communications are 1:1 between the master node and slave nodes.
All slave nodes receive part of the data sent by the master node (1a in figure).
The master node receives all data sent by the slaves. The data sizes are fixed
for all nodes.
Each slave nodes receives data from the previous node and then sends data
to the next node. Data is thus passed in ascending order of the nodes
participating in the data link.
One area is selected from the bit-access areas (e.g., CIO Area) or
word-access areas (e.g., DM Area).
Data link areas are allocated in ascending order of node addresses.
Data link participation can be specified for each node.
New version (version 3.2)
Controller Link Units
Controller Support Boards
• CS1W-CLK21-V1
• 3G8F7-CLK21-V1 (-EV1)
• CS1W-CLK12-V1
• 3G8F7-CLK12-V1 (-EV1)
• CS1W-CLK52-V1
• 3G8F7-CLK52-V1 (-EV1)
• CJ1W-CLK21-V1
New version (version 3.2)
New version (version 3.2)
New version (version 3.2)