Version 3.2 Upgrade Information
The following tables outline the changes that have been made from version 3.1 to version 3.2 of the CX-
Programmer.
• New Models for Automatically Set Data Links
Previous version
(version 3.1)
With automatically set data
links, all nodes shared the
same data using the common
settings, i.e., the send size for
each node was the same, and
send/receive nodes were
always in the order of node
addresses.
Automatic Setting Procedure for Controller Link Networks
1. Go online with the PLC that is to be used as the polling node.
2. Select Data Link – Setup from the CX-Net.
If on the local network (i.e., if the network address is 0), select Controller Link and click the OK
Button.
The Data Link Component Dialog Box will be displayed.
3. Select Automatic Datalink Setup from the Online Menu.
Select Controller Link and click the OK Button.
The Automatic Datalink Dialog Box will be displayed.
4. In the Automatic Datalink Type Box, select Equality layout, Common type, 1 to 1 type, or Chain
type and set the automatic data link areas as shown below.
• Equality Layout (Previous Method)
This is the previous automatic data link type where all nodes are allocated the same sizes of data
links.
A
G
1
3
6
5
H
With automatically set data links for Controller Link Networks, 1:N allocations are supported
in which data communications are set individually for the master node and slave nodes. (The
models that support this functionality are listed below.)
Any of the following four settings (data link patterns) can be used for automatic data links.
Equality layout (previous method), common type, 1 to 1 type, or chain type
• CS1W-CLK21-V1
Applicable
• CS1W-CLK12
models:
• CS1W-CLK52-V1
• CJ1W-CLK21-V1
Note: The 1:N allocations for automatic data links cannot be used with any other models.
Refer to the Controller Link Operation Manual for details.
Settings Common to All Automatic Data Link Types
B
C
D
E
F
2
4
New version (version 3.2)
• 3G8F7-CLK21-EV1
• 3G8F7-CLK12-EV1
V1
-
• 3G8F7-CLK52-EV1
No.
Item
Description of function
A
Generation
Select Automatic. (If Manual is selected, data links will
Type
be run using data link tables set separately.)
B
Power Up
Select Start to automatically start data links when power
Run State
is turned ON to the PLC.
C
Close
Closes the Automatic Datalink Dialog Box.
D
Read
Reads the settings from the PLC.
E
Write
Writes the settings to the PLC.
(If the Power Up Run State is set to Start, the data links
will start running when the settings are written to the
PLC.)
F
Help
Displays help.
G
Automatic
Select the type of data links to be automatically set up
Datalink
from the following.
Type
Equality Layout (Previous method)
Common Type (1:N settings)
1 to 1 Type (1:N settings)
Chain Type (1:N settings)
H
Result
The status is displayed when the Read or Write Button is
clicked.
PART 1: CX-Programmer
CX-Programmer_Page (xxxiv)