OMRON
5
The data link tables will be transferred.
6
The transfer results will be displayed.
Transferring to Individual Nodes on the Network
1
Select the transfer destination node address from the Node list in the Datalink Component.
Make sure that Set All Nodes for Network Operation is not selected in the Online menu.
Note:
As long as all the data link tables can be transferred to all of the PLCs attempted, Set All
Nodes for Network Operation can be selected to transfer the data link tables
simultaneously to multiple PLCs. If there are any PLCs with the power turned OFF, or
with disconnected cables, use the following method to transfer the data link table to one
PLC at a time.
Note:
• CX-Programmer (CX-Net) Ver. 3.2 or later is required to use the
Controller Link Support Board as a Network Support Board (NSB).
• When using a SYSMAC Link Support Board or CX-Programmer
(CX-Net) Ver. 3.1 or earlier, data link tables can be transferred only to
a single Network Support Board (NSB) node. Always use the
following method to transfer data link tables to all the nodes on the
network.
1. Use the mouse to select any node other than the Network
Support Board in the Data Link Configuration window or the
Node Editing window of the Datalink Component window.
2. Select Set All Nodes for Network Operation from the Online
menu in the Data Component window.
3. Select Transfer to PLC from the Online menu.
4. The data link tables are transferred after the check is completed.
PART 2: CX-Server PLC Tools
CHAPTER 10 – Data Links
CX-Server PLC Tools_ Page 121