PART 2: CX-Server PLC Tools
CHAPTER 11 – Routing Tables

Adding a Local Network

Use the following procedure to add a local network to a routing table.
1, 2, 3...
Note: The serial port of the CPU Unit and the serial port of the Serial Communications Board/Unit
CX-Server PLC Tools_Page 134
2.
In the Create Project dialog enter a file name for the new table, navigate to the
folder where the file is to be saved and click the Save button.
3.
From the PLC Network Configuration Tool Project menu select Add Device.
4.
In the Add PLC dialog Enter a Device Name and select a Device Type and
Network Type from the dropdown menu. And click OK.
5.
From the PLC Network Configuration Tool click on the device name in the
Project Device window.
6.
From the Routing Table menu, select Editor and then the required network type.
1.
Open the PLC Routing Table window and select the SIOU tab in the left hand
pane and the Main View tab in the right hand pane.
2.
Select the Unit from the SIOU list to which the local network is to be added then
right click on the that unit and select the Insert CPU SIOU option.
3.
From the Enter SIOU Details dialog enter the:
Local Network Number. This is the ID number that uniquely identifies the
local network in the routing table. Each new network must be given a unique ID
number in the range of 1 to 127.
Local Network Type. Select the type of local network from the drop down
menu. The network type selected will be displayed in the diagram.
4.
Click OK to close the SIOU dialog and add the local network to the selected
unit.
(unit version 1.2 or later) are displayed in the Unit directory in the SIOU Tab on the left.
Right-click and select Insert CPU SIOU to set the local network address in the serial port and
register in the local network table.
The serial port's unit number as a CPU Bus Unit or Special I/O Unit are automatically allocated
and cannot be changed.
The Unit and the Unit's serial port cannot be registered in the local network table at the same
time.