Note: The default setting for data link status depends on the PLC being used. For details, refer to the
PLC
CS/CJ Series
CVM1/CV Series
C200HX/HG/HE
CQM1H Series
7
Set node address 01 as shown in the following table, and then click the Next button or press the Enter key. Set
node addresses 02 and 03 in the same way.
Item
Area 1 start address
Area 2 start address
Area 1 local node send size (in words)
Area 2 local node send size (in words)
Data link status memory area (See note.)
Node Refresh Sequence
Beginning with the data link start address above, specify which nodes are to
have data refreshed at the local node address and the order in which data is to
be refreshed (i.e., the node refresh sequence). This order will be the same for
Area 1 and Area 2.
(For the local node address, data is sent from the local node area. For a
remote node address, data is received from the remote node address to the
local area.)
Note: • The local node must be included in the refresh nodes.
Example: If 1, 2, 3 is input, node addresses 1, 2, and 3 will be allocated in
order, beginning with the start address.
Click this button to make the values set for the above items the default values
for new data link settings.
Click to proceed to the next dialog box.
Controller Link Units Operation Manual (W309).
The data link status is contained in the 16 words (fixed) from CIO 1500 +25 × unit number + 7
to 22 in the CPU Bus Unit Area.
15
8 7
+7 words
Node 2
...
...
+22 words
Node 32
The data link status for node addresses 1 to 6 only is contained in the words from SR 239 to
SR 241, and SR 241 to SR 245.
Network 0
Network 1 15
SR 239
SR 243
Node 2
SR 240
SR 244
Node 4
SR 241
SR 245
Node 6
The data link status for node addresses 1 to 6 only is contained in the words from IR 91 to IR
93.
15
8 7
IR 91
Node 2
IR 92
Node 4
IR 93
Node 6
Item
Node address
PLC type
Area 1
Memory area
Start address
Send size
Area 2
Memory area
Start address
Send size
Function
• If the address of any node participating in the data links is not entered
here, data will not be received from that node.
Data link status
0
Node 1
...
Node 31
8 7
0
Node 1
Node 3
Node 5
0
Node 1
Node 3
Node 5
Data set
1
CS1G-CPU45
CIO
1000
30
D
500
30
PART 2: CX-Server PLC Tools
CHAPTER 10 – Data Links
Description
Sets CIO 1000 as the data link start
address for the Area 1 local node.
Sets 30 words as the send size (unit:
words) for the Area 1 local node.
Sets D00500 as the data link start
address for the Area 2 local node.
Sets 30 words as the send size (unit:
words) for the Area 2 local node.
CX-Server PLC Tools_ Page 101