Table 31. Maximum shock pulse specifications for the system 
Maximum shock pulse
Operating
Operating (Navy)
Storage
Particulate and gaseous contamination specifications
The following table defines the limitations that help avoid any equipment damage or failure from particulates and gaseous
contamination. If the levels of particulates or gaseous pollution exceed the specified limitations and result in equipment damage
or failure, you may need to rectify the environmental conditions. Remediation of environmental conditions is the responsibility of
the customer.
Table 32. Particulate contamination specifications 
Particulate contamination
Air filtration
Conductive dust
Corrosive dust
Walk-Up Edge Data Center or Cabinet (sealed, closed
loop environment)
Table 33. Gaseous contamination specifications 
Gaseous contamination
Copper coupon corrosion rate
Silver coupon corrosion rate
38
Technical specifications
Specifications
● Six consecutively executed shock pulses in the positive and negative x,
y, and z axes of 6 G for up to 11 ms.(4 pulse on each side of the system)
● For Military (with Military tool kit)
○ Method 516.8 Procedure I, 40G, 11ms, 3 shocks, +-per direction, 3
axes
MIL-STD-901E, Grade A, Class 2, Type A, in approved military transit case
● Six consecutively executed shock pulses in the positive and negative x,
y, and z axis (one pulse on each side of the system) of 71 G for up to 2
ms.
● For Military (with Military tool kit)
○ Method 516.8 Procedure V, 40G, 11ms, 3 shocks, +-per direction, 3
axes
Specifications
Data center air filtration as defined by ISO Class 8 per ISO 14644-1
with a 95% upper confidence limit
NOTE:
This condition applies to data center environments only. Air
filtration requirements do not apply to IT equipment designed to be
used outside a data center, in environments such as an office or
factory floor.
NOTE:
Air entering the data center must have MERV11 or MERV13
filtration.
Air must be free of conductive dust, zinc whiskers, or other
conductive particles
NOTE:
This condition applies to data center and non-data center
environments.
● Air must be free of corrosive dust
● Residual dust present in the air must have a deliquescent point less
than 60% relative humidity
NOTE:
This condition applies to data center and non-data center
environments.
Filtration is not required for cabinets that are anticipated to be opened
6 times or less per year. Class 8 per ISO 1466-1 filtration as defined
above is required otherwise
NOTE:
In environments commonly above ISA-71 Class G1 or that
may have known challenges, special filters may be required.
Specifications
<300 Å/month per Class G1 as defined by ANSI/ISA71.04-2013
<200 Å/month as defined by ANSI/ISA71.04-2013