10.5.4 Additional zone
Installer reference guide
132
INFORMATION
During defrost operation, the shut-off valve is ALWAYS opened.
During thermo: If [F‑0B] is enabled, the shut off valve closes when there is no
heating demand from the main zone. Enable this setting to:
▪
avoid leaving water supply to the heat emitters in the main LWT zone (through
the mixing valve station) when there is request from the additional LWT zone.
▪
activate the ON/OFF pump of the mixing valve station ONLY when there is
demand.
#
Code
[2.D.1]
[F-0B]
INFORMATION
The setting [F‑0B] is only valid when there is a thermostat or external room
thermostat request setting (NOT in case of leaving water temperature setting).
Setpoint screen
Control the leaving water temperature for the additional zone via setpoint screen
[3] Additional zone.
See
"10.3.5 Setpoint
screen" [
Schedule
Indicates if the desired leaving water temperature is according to a schedule.
See
"10.5.3 Main
zone" [
#
Code
[3.1]
N/A
Heating schedule
Define a heating temperature schedule for the additional zone via [3.2] Heating
schedule.
See
"10.3.7 Schedule screen:
Cooling schedule
Define a cooling temperature schedule for the additional zone via [3.3] Cooling
schedule.
See
"10.3.7 Schedule screen:
Setpoint mode
The setpoint mode of the additional zone can be independently set from the
setpoint mode of the main zone.
The shut off valve:
▪
0 No: is NOT influenced by heating or cooling
demand.
▪
1 Yes: closes when there is NO heating or
cooling demand.
4
109].
4
123].
Schedule:
▪
No
▪
Yes
4
Example" [
110].
4
Example" [
110].
Description
Description