15.1.3 Recovery mode

EPGA11~16DAV3(7) + EAVH/X16S18+23DA6V(7)+9W(7)
Daikin Altherma 3 H F
4P556070-1A – 2021.09
3 Turn the EEV magnet anticlockwise to the fully open position of the valve. If
you are not sure about what the open position is, turn the valve in its middle
position so that refrigerant can pass.
Before recovering refrigerant, make sure the electronic expansion valves are open.
When power is ON, this has to be done by using the recovery mode.
Components
To activate/deactivate the recovery mode, you need the following components:
H1P
H2P
H3P
MODE
TEST
HWL
BS1
BS2
MODE
SET
H1P~H7P 7‑LEDs display
BS1~BS4 Push buttons. Operate the push buttons with an insulated stick (such as a closed
ballpoint pen) to avoid touching of live parts.
To activate the recovery mode
INFORMATION
If you get confused in the middle of the process, press BS1 to return to the default
situation.
Before recovering refrigerant, activate the recovery mode as follows:
#
Action
1
Start from the default situation.
2
Press and hold BS1 for 5 seconds.
3
Press BS2 9 times.
4
Press BS3 once.
5
Press BS2 once.
6
Press BS3 once.
H4P
H5P
H6P
H7P
L.N.O.P.
DEMAND
BS3
BS4
RETURN
PUMP DOWN
H1P H2P H3P H4P H5P H6P H7P
15
Disposal
|
(a)
7-LEDs display
Installer reference guide
203