Additional Zone - Daikin Altherma 3 R MT F Series Installer's Reference Manual

Table of Contents

Advertisement

11
|
Configuration

11.6.4 Additional zone

Installer reference guide
184
#
Code
[2.D.1]
[F-0B]
INFORMATION
The setting [F‑0B] is only valid when there is a thermostat or external room
thermostat request setting (NOT in case of leaving water temperature setting).
During cooling: If [F‑0B] is enabled, the shut off valve closes when the unit is
running in cooling operation mode. Enable this setting to avoid cold leaving water
through the heat emitter and the forming of condensation (e.g. under floor heating
loops or radiators).
#
Code
[2.D.2]
[F-0C]
WD curve type
The weather-dependent curve can be defined using the 2-points method or the
Slope-Offset method.
See
"11.5.2 2-points
curve" [
#
Code
[2.E]
N/A
Overview
The following items are listed in the submenu:
The shut off valve:
0 No: is NOT influenced by heating or cooling
demand.
1 Yes: closes when there is NO heating or
cooling demand.
The shut off valve:
0 No: is NOT influenced by changing the space
operation mode to cooling.
1 Yes: closes when the space operation mode
is cooling.
4
 164] and
"11.5.3 Slope-offset
2-points
Slope-Offset
Description
Description
4
curve" [
 165].
Description
ERRA08~12E + ELVZ12S18+23E
Daikin Altherma 3 R MT F
4P708478-1 – 2023.05