Electrical installation

9.3.2 To connect the backup heater power supply

Installer reference guide
92
2 Fix the cables with cable ties to the cable tie mountings.
INFORMATION
In case of preferential kWh rate power supply, connect X11Y to X11YB. The necessity
of separate normal kWh rate power supply to indoor unit (b) X2M/5+6 depends on
the type of preferential kWh rate power supply.
Separate connection to the indoor unit is required:
if preferential kWh rate power supply is interrupted when active, OR
if no power consumption of the indoor unit is allowed at the preferential kWh
rate power supply when active.
INFORMATION
The preferential kWh rate power supply contact is connected to the same terminals
(X5M/9+10) as the safety thermostat. Thus, the system can have EITHER preferential
kWh rate power supply OR a safety thermostat.
WARNING
The backup heater MUST have a dedicated power supply and MUST be protected by
the safety devices required by the applicable legislation.
CAUTION
To guarantee the unit is completely earthed, ALWAYS connect the backup heater
power supply and the earth cable.
The backup heater capacity can vary, depending on the indoor unit model. Make
sure that the power supply is in accordance with the backup heater capacity, as
listed in the table below.
Backup heater
Backup
type
capacity
*6V
*9W
(a)
6V3
(b)
Electrical equipment complying with EN/IEC 61000-3-12 (European/International Technical
Standard setting the limits for harmonic currents produced by equipment connected to
public low-voltage systems with input current >16 A and ≤75 A per phase).
Power supply
heater
2 kW
1N~ 230 V
4 kW
1N~ 230 V
6 kW
1N~ 230 V
2 kW
3~ 230 V
4 kW
3~ 230 V
6 kW
3~ 230 V
3 kW
3N~ 400 V
6 kW
3N~ 400 V
9 kW
3N~ 400 V
Maximum
running current
(a)
9 A
(a)
(b)(c)
17 A
(a)
(b)(c)
26 A
(d)
5 A
(d)
10 A
(d)
15 A
4 A
9 A
13 A
EPGA11~16DAV3(7) + EAVH/X16S18+23DA6V(7)+9W(7)
4P556070-1A – 2021.09
Z
max
0.22 Ω
0.22 Ω