Heat pump convectors
EPGA11~16DAV3(7) + EAVH/X16S18+23DA6V(7)+9W(7)
Daikin Altherma 3 H F
4P556070-1A – 2021.09
▪
Efficiency. Although the external room thermostat only sends ON/OFF signals, it
is specifically designed for the heat pump system.
▪
Comfort. In case of underfloor heating, the wireless external room thermostat
prevents condensation on the floor during cooling operation by measuring the
room humidity.
Setup
A Main leaving water temperature zone
B One single room
a Remote controller of the heat pump convectors
▪
The heat pump convectors are directly connected to the indoor unit.
▪
The desired room temperature is set via the remote controller of the heat pump
convectors.
▪
The space heating/cooling demand signal is sent to one digital input on the
indoor unit (X2M/35 and X2M/30).
▪
The space operation mode is sent to the heat pump convectors by one digital
output on the indoor unit (X2M/4 and X2M/3).
INFORMATION
When using multiple heat pump convectors, make sure each one receives the
infrared signal from the remote controller of the heat pump convectors.
Configuration
Setting
Unit temperature control:
▪
#: [2.9]
▪
Code: [C-07]
Number of water temperature zones:
▪
#: [4.4]
▪
Code: [7-02]
External room thermostat for the main
zone:
▪
#: [2.A]
▪
Code: [C-05]
6
Application guidelines
|
B
A
a
Value
1 (External room thermostat):
Unit operation is decided by the
external thermostat.
0 (Single zone): Main
1 (1 contact): When the used
external room thermostat or heat pump
convector can only send a thermo ON/
OFF condition. No separation between
heating or cooling demand.
Installer reference guide
33