8.1.5 To check the water volume: Examples

8.2 Connecting water piping

8.2.1 About connecting the water piping

EPGA11~16DAV3(7) + EAVH/X16S18+23DA6V(7)+9W(7)
Daikin Altherma 3 H F
4P556070-1A – 2021.09
Only use dry nitrogen to set the expansion vessel pre-pressure.
Inappropriate setting of the expansion vessel pre-pressure will lead to
malfunction of the system.
Changing the pre-pressure of the expansion vessel should be done by releasing or
increasing nitrogen pressure through the Schrader valve of the expansion vessel.
a Schrader valve
Example 1
The indoor unit is installed 5  m below the highest point in the water circuit. The
total water volume in the water circuit is 100 l.
No actions or adjustments are required.
Example 2
The indoor unit is installed at the highest point in the water circuit. The total water
volume in the water circuit is 250 l.
Actions:
Because the total water volume (250  l) is more than the default water volume
(200 l), the pre-pressure must be decreased.
The required pre-pressure is:
Pg = (0.3+(H/10)) bar = (0.3+(0/10)) bar = 0.3 bar
The corresponding maximum water volume at 0.3 bar is 290 l. (See the graph in
"Maximum water
volume" [
Because 250  l is lower than 290  l, the expansion vessel is appropriate for the
installation.
Before connecting the water piping
Make sure the outdoor and indoor unit are mounted.
4
 75]).