Daikin EAVH16S23DA6V Installer's Reference Manual page 135

Hide thumbs Also See for EAVH16S23DA6V:
Table of Contents

Advertisement

EPGA11~16DAV3(7) + EAVH/X16S18+23DA6V(7)+9W(7)
Daikin Altherma 3 H F
4P556070-1A – 2021.09
Setpoint range
For more information about Setpoint range, see
#
Code
Leaving water temperature range for the additional leaving water temperature
zone (= the leaving water temperature zone with the highest leaving water
temperature in heating operation and the lowest leaving water temperature in
cooling operation)
[3.8.1]
[9-05]
[3.8.2]
[9-06]
[3.8.3]
[9-07]
[3.8.4]
[9-08]
Control
The control type for the additional zone is read only. It is determined by the control
type of the main zone.
See
"10.5.3 Main
zone" [
#
Code
[3.9]
N/A
Thermostat type
Only applicable in external room thermostat control.
Also see
"10.5.3 Main
zone" [
#
Code
[3.A]
[C‑06]
Leaving water temperature: Delta T
For more information, see
Heating minimum: 15°C~37°C
Heating maximum
[2‑0D]=2 (emitter type additional zone =
radiator)
37°C~60°C
Else: 37°C~55°C
Cooling minimum
5°C~18°C
Cooling maximum
18°C~22°C
4
 123].
Control:
Leaving
water if the control type of the
main zone is Leaving water.
External room thermostat if the control
type of the main zone is:
-
External room thermostat,or
-
Room thermostat.
4
 123].
External room thermostat type for the additional
zone:
1: 1
contact. Connected to only 1 digital
input (X2M/35a)
2: 2 contacts. Connected to 2 digital inputs
(X2M/34a and X2M/35a)
4
"10.5.3 Main
zone" [
10
Configuration
|
"10.5.3 Main
zone" [
Description
Description
Description
 123].
Installer reference guide
4
 123].
135