Daikin EAVH16S23DA6V Installer's Reference Manual page 37

Hide thumbs Also See for EAVH16S23DA6V:
Table of Contents

Advertisement

Heat pump convectors – Multiple rooms
EPGA11~16DAV3(7) + EAVH/X16S18+23DA6V(7)+9W(7)
Daikin Altherma 3 H F
4P556070-1A – 2021.09
Configuration
Setting
Unit temperature control:
#: [2.9]
Code: [C-07]
Number of water temperature zones:
#: [4.4]
Code: [7-02]
Benefits
Compared with underfloor heating or radiators for one room:
Comfort. You can set the desired room temperature, including schedules, for
each room via the room thermostats.
Setup
A Main leaving water temperature zone
B Room 1
C Room 2
a Remote controller of the heat pump convectors
The desired room temperature is set via the remote controller of the heat pump
convectors.
The user interface integrated in the indoor unit decides the space operation
mode.
The heating or cooling demand signals of each heat  pump convector are
connected in parallel to the digital input on the indoor unit (X2M/35 and
X2M/30). The indoor unit will only supply leaving water temperature when there
is an actual demand.
INFORMATION
To increase comfort and performance, we recommend to install the valve kit option
EKVKHPC on each heat pump convector.
Configuration
Setting
Unit temperature control:
#: [2.9]
Code: [C-07]
6
Application guidelines
|
Value
0 (Leaving water): Unit operation is
decided based on the leaving water
temperature.
0 (Single zone): Main
B
C
A
a
a
Value
1 (External room thermostat):
Unit operation is decided by the
external thermostat.
Installer reference guide
37