10.5.3 Main zone

EPGA11~16DAV3(7) + EAVH/X16S18+23DA6V(7)+9W(7)
Daikin Altherma 3 H F
4P556070-1A – 2021.09
NOTICE
If Emergency is set to Manual ([9.5]=0), and the unit is triggered to start emergency
operation, the unit will stop and need to be recovered manually via the user
interface. To recover operation manually, go to the Malfunctioning main menu
screen, where the user interface will then ask you to confirm emergency operation
before starting.
Room frost protection is active even if the user does NOT confirm emergency
operation.
Setpoint range
Only applicable in room thermostat control.
To save energy by preventing overheating or undercooling the room, you can limit
the range of the room temperature for heating and/or cooling.
NOTICE
When adjusting the room temperature ranges, all desired room temperatures are
also adjusted to guarantee they are between the limits.
#
Code
[1.5.1]
[3-07]
[1.5.2]
[3-06]
[1.5.3]
[3-09]
[1.5.4]
[3-08]
Room sensor offset
Only applicable in room thermostat control.
To calibrate the (external) room temperature sensor, give an offset to the value of
the room thermistor as measured by the user interface used as room thermostat
or by the external room sensor. The setting can be used to compensate for
situations where the user interface used as room thermostat or the external room
sensor cannot be installed at the ideal location.
See
"6.7 Setting up an external temperature
#
Code
[1.6]
[2-0A]
[1.7]
[2-09]
Setpoint screen
Control the leaving water temperature for the main zone via setpoint screen [2]

Main zone.

See
"10.3.5 Setpoint
screen" [
Description
Heating minimum
Heating maximum
Cooling minimum
Cooling maximum
sensor" [
Description
Room sensor offset (user interface used as
room thermostat): Offset on the actual room
temperature measured by the user interface
used as room thermostat.
–5°C~5°C, step 0.5°C
Room sensor offset (external room sensor
option): Only applicable if the external room
sensor option is installed and configured.
–5°C~5°C, step 0.5°C
4
 109].
10
Configuration
|
4
 54]).
Installer reference guide
123