Daikin EAVH16S23DA6V Installer's Reference Manual page 38

Hide thumbs Also See for EAVH16S23DA6V:
Table of Contents

Advertisement

6
|
Application guidelines
Combination: Underfloor heating + Heat pump convectors – Multiple rooms
Installer reference guide
38
Setting
Number of water temperature zones:
#: [4.4]
Code: [7-02]
Benefits
Compared with heat pump convectors for one room:
Comfort. You can set the desired room temperature, including schedules, for
each room via the remote controller of the heat pump convectors.
Setup
A Main leaving water temperature zone
B Room 1
C Room 2
a External room thermostat
b Remote controller of the heat pump convectors
For each room with heat  pump convectors: The heat  pump convectors are
directly connected to the indoor unit.
For each room with underfloor heating: Two shut-off valves (field supply) are
installed before the underfloor heating:
-
A shut-off valve to prevent hot water supply when the room has no heating
demand
-
A shut-off valve to prevent condensation on the floor during cooling operation
of the rooms with heat pump convectors.
For each room with heat pump convectors: The desired room temperature is set
via the remote controller of the heat pump convectors.
For each room with underfloor heating: The desired room temperature is set via
the external room thermostat (wired or wireless).
The user interface integrated in the indoor unit decides the space operation
mode. Mind that the operation mode on each external room thermostat and
remote controller of the heat pump convectors must be set to match the indoor
unit.
INFORMATION
To increase comfort and performance, we recommend to install the valve kit option
EKVKHPC on each heat pump convector.
0 (Single zone): Main
B
C
A
M1
M1
b
a
EPGA11~16DAV3(7) + EAVH/X16S18+23DA6V(7)+9W(7)
Value
Daikin Altherma 3 H F
4P556070-1A – 2021.09