15 Disposal

In this chapter

15.1 To recover refrigerant

EPGA11~16DAV3(7) + EAVH/X16S18+23DA6V(7)+9W(7)
Daikin Altherma 3 H F
4P556070-1A – 2021.09
NOTICE
Do NOT try to dismantle the system yourself: dismantling of the system, treatment of
the refrigerant, oil and other parts MUST comply with applicable legislation. Units
MUST be treated at a specialised treatment facility for reuse, recycling and recovery.
15.1
To recover refrigerant ............................................................................................................................................................ 201
15.1.1
To open the stop valves ......................................................................................................................................... 202
15.1.2
To manually open the electronic expansion valves............................................................................................... 202
15.1.3
Recovery mode....................................................................................................................................................... 203
When disposing of the outdoor unit, you need to recover its refrigerant.
To ensure that no refrigerant remains trapped in the unit:
Make sure the stop valves are open (a, b).
Make sure the valves (Y1E, Y3E, Y2S, Y3S) are open.
Use all 3 service ports (a, b, c) to recover refrigerant.
Components
a
a Liquid stop valve with service port
b Gas stop valve with service port
c Service port 5/16" flare
Y1E Electronic expansion valve (main)
Y3E Electronic expansion valve (injection)
Y2S Solenoid valve (injection bypass)
Y3S Solenoid valve (hot gas bypass)
Y2S + Y3S
c
b
Y1E
Y3E
15
Disposal
|
Installer reference guide
201