Maintenance Precautions; Fru Removal And Installation Flow - Fujitsu M10-4 Service Manual

Hide thumbs Also See for M10-4:
Table of Contents

Advertisement

9.3

Maintenance Precautions

Note the following points when you maintain the CPU memory unit:
Caution - The weight of the CPU memory unit is 17 kg (37.4 lb). If the mounting
location in the rack is 24U or higher, the maintenance work must be done by two
people. If you attempt to perform the maintenance work alone, you may injure
yourself or cause damage to the chassis.
Do not replace the CPU memory unit lower at the same time as the PSU backplane
unit. If you replace them at the same time, the system may fail to operate normally.
Do not mount and use any of the following microSD cards in the CPU memory
unit lower in another chassis:
- the one currently mounted in the SPARC M10-4/M10-4S, or
- one that was once used as a maintenance part
This is because these microSD cards store device identification information.
The XSCF mounted in the CPU memory unit lower is not a FRU (field replaceable
unit). When replacing the CPU memory unit lower, do not switch the XSCF units.
If you switch the microSD card when replacing the CPU memory unit lower, the
maintenance time is shorter since the XSCF setting information is inherited.
If you replace the microSD card along with the CPU memory unit lower, dispose
of the microSD card mounted on the old CPU memory unit lower by appropriate
means such as cutting it with cutting pliers. The old microSD card stores the user
information, IP address, and other information set in the XSCF firmware.
If the device uses the hardware RAID function, after replacing the CPU memory
unit lower, you need to reactivate the hardware RAID volume. For details, see
"14.2.11 Re-enabling a Hardware RAID Volume" in the Fujitsu SPARC M12 and
Fujitsu M10/SPARC M10 System Operation and Administration Guide.
When installing the CPU memory unit upper, you need to perform the work of
adding PCIe cables. For details, see
When you install/remove the CPU memory unit upper, the root complex is also
installed/removed. As a result, the PCIe card installation rules, etc. may change
and the logical domains may need to be reconfigured. For details, see
Precautions for
9.4

FRU Removal and Installation Flow

Perform maintenance work on the CPU memory unit by following the procedures
shown in
218
Fujitsu M10-4/Fujitsu M10-4S/SPARC M10-4/SPARC M10-4S Service Manual ・ June 2023
installation" or
Figure 9-3
and
Table
9-1.
"9.6 Installing a PCI Express
"4.3.3 Precautions for
Cable."
"4.3.2
reduction."