Press the power switch on the operation panel for 1 second or more (less
2.
than 4 seconds).
For details, see
"2.3.2 Control function of the operation
Note - For a building block configuration, press the power switch on the master chassis. The
power switches of the other chassis are disabled.
3.
Confirm that the POWER LED on the operation panel is on.
4.
Execute the showpparstatus command to confirm that the power to all the
physical partitions in the system is turned on.
Confirm that no error remains by using the fmadm faulty command in the
5.
logical domain in which an error was detected.
# fmadm faulty
If any error remains, clear the error by using the fmadm repaired command.
panel."
Chapter 6 Restoring the System