82 Chapter 7 Replacing basic chassis components

Replacing a hard drive

The 600r server has one SCSI drive. You do not need to remove the server
cover to add or replace a hard drive, but you must remove the front bezel.
You must replace the hard drive with an identical unit or other Nortel-approved
hard drive.

To replace a SCSI hard drive

Step
1
2
3
4
5
6
Copyright © 2007, Nortel Networks
.
Action
Power down the server, unplug all peripheral devices and Ethernet
cables, and disconnect the AC power.
Remove the front bezel. For more instructions, see
replacing the front bezel" (page
Attach the ESD strap to your wrist and attach the other end to a
known grounded connection.
Press in on the green latch on the front of the hard drive carrier as
shown in the following diagram.
Figure 21
SCSI hard drive carrier
Pull out on the black lever to slide the carrier from the chassis.
Remove the four screws that attach the plastic retention device or
the previously installed hard drive to the drive carrier. Two screws
are at each side of the retention device or the hard drive. Store the
plastic retention device for future use.

Nortel CallPilot

600r Server Maintenance and Diagnostics

NN44200-703 01.04 Standard

5.0 25 April 2007