Appendix G: Communications Via Profibus Pa; Device Configuration Tool; Simatic Pdm; Device Description (Dd) - Siemens sitrans LR200 Instruction Manual

2-wire, 6 ghz pulse radar level transmitter
Hide thumbs Also See for sitrans LR200:
Table of Contents

Advertisement

Appendix G: Communications via
PROFIBUS PA
SITRANS LR200 (PROFIBUS PA) is a Profile Version 3.01, Class B, PA device. It supports
Class 1 Master for cyclic and acyclic data exchange, and Class 2 for acyclic services.
The full range of SITRANS LR200 functions is available only over a PROFIBUS PA
network.
PROFIBUS PA is an open industrial protocol. Full details about PROFIBUS PA can be
obtained from PROFIBUS International at www.profibus.com.

Device Configuration Tool

To use PROFIBUS PA, you will need a PC configuration tool: we recommend SIMATIC
PDM. Please consult the operating instructions or online help for details on using
SIMATIC PDM. (You can find more information at www.fielddevices.com: go to Products
and Solutions > Products and Systems > Communications and Software Process Device
Manager.)

SIMATIC PDM

SIMATIC PDM is a software package used to commission and maintain SITRANS LR200
and other process devices. For more detail see

Device Description (DD)

In order to use Process Device Manager (PDM) with PROFIBUS PA, you will need the
Device Description for SITRANS LR200 (PROFIBUS PA). For details, see
Description (DD)

Network Configuration

To configure a PROFIBUS PA Class 1 Master (for example, a PLC), you will need a GSD
file.

The GSD file

The GSD file SIEM810F.gsd is available from the SITRANS LR200 product page on our
web site. Go to www.siemens.com/LR200 and click on Downloads. Download the
DeviceInstall, and run it from your computer. This will install the GSD file into your system
(as long as you are using SIMATIC software).
Page 128
SITRANS LR200 (PROFIBUS PA) – INSTRUCTION MANUAL
on page 29.
Operating via SIMATIC PDM
on page 28.
Device
7ML19985JR01

Advertisement

Table of Contents
loading