NOTES ON TEMPERATURE ADJUSTMENT

The heating and cooling devices are managed on the basis of the temperature values measured by the return or delivery probe depending on the parameter settings. This
temperature is compared with the set value (setpoint), and based on the difference, the devices may activate. The proportional band selects the working area and may
assume (as for the setpoints) different heating and cooling values.
The software can be used to manage three temperature adjustment types:
Purely Proportional adjustment;
Proportional + Integral adjustment;
Proportional + Integral + Derived adjustment (only in units with inverter compressor).
The basic programme setting (default) features Proportional + Integral adjustment with an elevated integral time constant, therefore very close to purely proportional
adjustment.
All the adjustment diagrams shown in this manual refer to a purely proportional adjustment.
Compared with the diagrams described further on, Proportional + Integral adjustment can reduce (with respect to the distance between ambient temperature and setpoint)
the activation time of the cooling and heating devices and consequently delay shutdown. This effect is more marked the longer the "permanent off-balance" phenomenon
continues, that is, the immobility of the ambient temperature in a different point from the set setpoint. In any case, the delay/anticipation of the unit enable/disable never goes
beyond the limit of the opposite proportional band.
Integral adjustment is inhibited (and therefore pure proportional adjustment is active) when the two cold and hot setpoints are set, so that a dead zone is included (when the
two setpoints are different). In this case, no adjustment resources must ever be enabled in the temperature zone between the two setpoints; the integral adjustment delay is
therefore disabled;
4.1

MANAGEMENT OF THE LIMITS OF THE COLD SETPOINT

The parameter for setting the setpoint is automatically limited to specific values set during the design of the units themselves.
The set values are given in the table below.
Unit code
s-MEXT DX/DW
The parameters P20.24 and P20.25 are in the "Regulation" menu, which can be accessed by entering the "Service" password.
INFORMATION
Although the parameters P20.24 and P20.25 can be accessed with the "Service" password, please contact MEHITS before setting different values.
When the unit is equipped with heating sources (electric heaters or hot water coil), the minimum allowable setpoint value is limited by the value of the hot setpoint value.
The chart below illustrates the limitation described above.
4.2

REGULATION PROBE MANAGEMENT

For the unit, it is possible to define which probe to use for the adjustment, selecting from:
Intake air probe.
Delivery air probe.
The regulation with delivery air probe is allowed only if the heaters are not present.
Technical manual
Description
Direct expansion to be used in combination with the Mr Slim condensing unit
P20.24
P20.24
Figure 4-1: Charts of management of the setpoint limits
Without Heating sources
Set
P20.25
P50.01
WITH Heating sources
Set
Set
P20.25
P50.02
P50.01
72
P20.24 (°C)
20
T
(°C)
ambient
T
(°C)
ambient
TRANSLATION OF THE ORIGINAL INSTRUCTIONS
P20.25 (°C)
32